AI040 – Analog Input

  • 4 analog inputs with IEPE interface
  • Signal conversion in frequency range of 31 mHz to 20 kHz (16 bits)
  • Max. sampling rate 50 kSPS
  • 5 µs offset between channels
  • Condition Monitoring

Dati sulle prestazioni

Supply voltage +24 V DC (+18-30 V DC)

IEPE Interfaces

Type IEPE interface
Amount 4
Measurement range ±0.172 … ±5.5 V AC
Resolution 16 bits
Conversion rate/channel ≥ 5 µs (adjustable, default setting 5 µs)
Data recording/channel maximum 64 Word
Short-circuit proof, current limited Yes
Cable break monitor Yes
Hardware filter typically 31 MHz (high pass 1st order), typically 20 kHz (low pass 3rd order)

Software Band Pass Filter

Lower frequency limit adjustable (minimum 0.1 Hz)
Upper frequency limit adjustable (maximum 10 kHz)
Processed measured values/cycle configurable
Output parameters Average Value, Minimum Value, Timestamp, Minimum Value, Timestamp, Maximum Value

Sensor Supply

Adjustable current 0, 4, 8, 12 mA individually adjustable for each channel
Supply voltage +18-30 V DC
Sensor voltage typically 19.1 V DC

Caratteristiche meccaniche

Dimensions 12.5 x 104 x 72 mm (W x H x D)
Protection type IP20

Numero articolo / certificazione

Article number 20-009-040
Standardization/­certification UL 508 (E247993)

Maggiori informazioni sui nostri prodotti?

Contattaci ora tramite questo form. Ti risponderemo il prima possibile!